Prices  UG-5-AFR-230V-ST2  Calectro  Turkey

BRAND Calectro
Product UG-5-AFR-230V-ST2
Description air channel smoke switch
Internal code IMP4687413
Weight 1.5
Custom code 85311030
Technical specification Calectro duct smoke detector 230 V AC The Calectro duct smoke detector was developed and combined to detect smoke in ventilation ducts a smoke detector with an adapter system, with pipe and housing specifically for optimal airflow designed by the smoke detector. The UG-5 can be used on each side of the channel in four different Positions can be installed: 0°, 90°, 180° and 270°. Patented. Complete delivery with air duct removal pipe, 0.6 m long. Power supply: 230 V AC -15%, +10% Smoke detector type: Optical UG-5-AFR-230V Max. power consumption: 30 mA Operating temperature: -10°C to +55°C Maximum humidity: 99% RH Air velocity range: 1 to 20 m/s Approvals: VdS G213014, CE, prEN-54-27 Smoke alarm release via remote reset Relay output: potential-free Smoke alarm relay: Two 250 V, 8A changeover contacts Service alarm: One 250 V, 5 A changeover contact System fault alarm: One 250 V, 5 A changeover contact Air speed alarm: One 250 V, 5 A changeover contact LED on smoke detector: Green: service alarm (contamination) red - smoke alarm LED on circuit board: Green: normal mode Yellow - system error Yellow - air speed alert Adapter housing: ABS Protection class: IP54